Wednesday, December 31, 2014

Distance Relay or Impedance Relay



"" This is Just an Example for a post ""

There is one type of relay which functions depending upon the distance of fault in the line. More specifically, the relay operates depending upon the impedance between the point of fault and the point where relay is installed. These relays are known as distance relay orimpedance relay.

Working Principle of Distance or Impedance Relay

The working principle of distance relay or impedance relay is very simple. There is one voltage element from potential transformer and an current element fed from current transformer of the system. The deflecting torque is produced by secondary current of CT and restoring torque is produced by voltage of potential transformer. In normal operating condition, restoring torque is more than deflecting torque. Hence relay will not operate. But in faulty condition, the current becomes quite large whereas voltage becomes less. Consequently, deflecting torque becomes more than restoring torque and dynamic parts of the relay starts moving which ultimately close the No contact of relay. Hence clearly operation or working principle of distance relay, depends upon the ratio of system voltage and current. As the ratio of voltage to current is nothing but impedance a distance relay is also known as impedance relay.
The operation of such relay depends upon the predetermined value of voltage to current ratio. This ratio is nothing but impedance. The relay will only operate when this voltage to current ratio becomes less than its predetermined value. Hence, it can be said that the relay will only operate when the impedance of the line becomes less than predetermined impedance (voltage / current). As the impedance of a transmission line is directly proportional to its length, it can easily be concluded that a distance relay can only operate if fault is occurred within a predetermined distance or length of line.

Types of Distance or Impedance Relay

There are mainly two types of distance relay-
  1. Definite distance relay.
  2. Time distance relay.
Let us discuss one by one.

Definite Distance Relay

This is simply a variety of balance beam relay. Here one beam is placed horizontally and supported by hinge on the middle. One end of the beam is pulled downward by the magnetic force of voltage coil, fed from potential transformer attached to the line. Other end of the beam is pulled downward by the magnetic force of current coil fed from current transformer connected in series with line. Due to torque produced by these two downward forces, the beam stays at an equilibrium position. The torque due to voltage coil, serves as restraining torque and torque due to current coil, serves as deflecting torque.
Under normal operating condition restraining torque is greater than deflecting torque. Hence contacts of this distance relay remain open. When any fault is occurred in the feeder, under protected zone, voltage of feeder decreases and at the same time current increases. The ratio of voltage to current i.e. impedance falls below the pre-determined value. In this situation, current coil pulls the beam more strongly than voltage coil, hence beam tilts to close the relay contacts and consequently the circuit breaker associated with this impedance relay will trip.

Time Distance Impedance Relay

This delay automatically adjusts its operating time according to the distance of the relay from the fault point. The time distance impedance relay not only be operated depending upon voltage to current ratio, its operating time also depends upon the value of this ratio. That means,

Construction of Time Distance Impedance Relay

time distance impedance relay

The relay mainly consists of a current driven element like double winding type induction over current relay. The spindle carrying the disc of this element is connected by means of a spiral spring coupling to a second spindle which carries the bridging piece of the relay contacts. The bridge is normally held in the open position by an armature held against the pole face of an electromagnet excited by the voltage of the circuit to be protected.

Operating Principle of Time Distance Impedance Relay

During normal operating condition the attraction force of armature fed from PT is more than force generated by induction element, hence relay contacts remain in open position when a short circuit fault occurs in the transmission line, the current in the induction element increases. Then the induction in the induction element increases. Then the induction element starts rotating. The speed of rotation of induction elements depends upon the level of fault i.e. quantity of current in the induction element. As the rotation of the disc proceeds, the spiral spring coupling is wound up till the tension of the spring is sufficient to pull the armature away from the pole face of the voltage excited magnet.
The angle through which the disc travels the disc travel before relay operate depends upon the pull of the voltage excited magnet. The greater the pull, the greater will be the travel of the disc. The pull of this magnet depends upon the line voltage. The greater the line voltage the greater the pull hence longer will be the travel of the disc i.e. operating time is proportional to V.
Again, speed of rotation of induction element approximately proportional to current in this element. Hence, time of operation is inversely proportional to current.


Therefore time of operation of relay,


Power System Protection



"This is Just an example for a post ""

This portion of our website covers almost everything related to protection system in power system including standard lead and device numbers, mode of connections at terminal strips, color codes in multi-core cables, Dos and Don’ts in execution. It also covers principles of various power system protection relays and schemes including special power system protection schemes like differential relays, restricted earth fault protection, directional relays and distance relays etc. The details of transformer protection, generator protection, transmission line protection & protection of capacitor banks are also given. It covers almost everything about protection of power system.

The switchgear testing, instrument transformers like current transformer testing voltage or potential transformer testing and associated protection relay are explained in detail. The close and trip, indication and alarm circuits different of circuit breakers are also included and explain.

Objective of Power System Protection

The objective of power system protection is to isolate a faulty section of electrical power system from rest of the live system so that the rest portion can function satisfactorily without any severer damage due to fault current.
Actually circuit breaker isolates the faulty system from rest of the healthy system and this circuit breakers automatically open during fault condition due to its trip signal comes from protection relay. The main philosophy about protection is that no protection of power system can prevent the flow of fault current through the system, it only can prevent the continuation of flowing of fault current by quickly disconnect the short circuit path from the system. For satisfying this quick disconnection the protection relays should have following functional requirements.

Protection System in Power System

Let’s have a discussion on basic concept of protection system in power system and coordination of protection relays.
power system protection relays


In the picture the basic connection of protection relay has been shown. It is quite simple. The secondary of current transformer is connected to the current coil of relay. And secondary of voltage transformer is connected to the voltage coil of the relay. Whenever any fault occurs in the feeder circuit, proportionate secondary current of the CT will flow through the current coil of the relay due to which mmf of that coil is increased. This increased mmf is sufficient to mechanically close the normally open contact of the relay. This relay contact actually closes and completes the DC trip coil circuit and hence the trip coil is energized. The mmf of the trip coil initiates the mechanical movement of the tripping mechanism of the circuit breaker and ultimately the circuit breaker is tripped to isolate the fault. 

Functional Requirements of Protection Relay

Reliability

The most important requisite of protective relay is reliability. They remain inoperative for a long time before a fault occurs; but if a fault occurs, the relays must respond instantly and correctly.

Selectivity

The relay must be operated in only those conditions for which relays are commissioned in the electrical power system. There may be some typical condition during fault for which some relays should not be operated or operated after some definite time delay hence protection relay must be sufficiently capable to select appropriate condition for which it would be operated.

Sensitivity

The relaying equipment must be sufficiently sensitive so that it can be operated reliably when level of fault condition just crosses the predefined limit.

Speed

The protective relays must operate at the required speed. There must be a correct coordination provided in various power system protection relays in such a way that for fault at one portion of the system should not disturb other healthy portion. Fault current may flow through a part of healthy portion since they are electrically connected but relays associated with that healthy portion should not be operated faster than the relays of faulty portion otherwise undesired interruption of healthy system may occur. Again if relay associated with faulty portion is not operated in proper time due to any defect in it or other reason, then only the next relay associated with the healthy portion of the system must be operated to isolate the fault. Hence it should neither be too slow which may result in damage to the equipment nor should it be too fast which may result in undesired operation.

Important Elements for Power System Protection

Switchgear

Consists of mainly bulk oil circuit breaker, minimum oil circuit breaker, SF6 circuit breaker, air blast circuit breaker and vacuum circuit breaker etc. Different operating mechanisms such as solenoid, spring, pneumatic, hydraulic etc. are employed in circuit breaker. Circuit breaker is the main part of protection system in power system it automatically isolate the faulty portion of the system by opening its contacts.

Protective Gear

Consists of mainly power system protection relays like current relays, voltage relays, impedance relays, power relays, frequency relays, etc. based on operating parameter, definite time relays, inverse time relays, stepped relays etc. as per operating characteristic, logic wise such as differential relays, over fluxing relays etc. During fault the protection relay gives trip signal to the associated circuit breaker for opening its contacts. 

Station Battery

All the circuit breakers of electrical power system are DC (Direct Current) operated. Because DC power can be stored in battery and if situation comes when total failure of incoming power occurs, still the circuit breakers can be operated for restoring the situation by the power of storage battery . Hence the battery is another essential item of the power system. Some time it is referred as the heart of the electrical substation. An electrical substation battery or simply a station battery containing a number of cells accumulate energy during the period of availability of A.C supply and discharge at the time when relays operate so that relevant circuit breaker is tripped.

Electrical Protection Relay


""Just an Example For a Post ""

Definition of Protective Relay

A relay is automatic device which senses an abnormal condition of electrical circuit and closes its contacts. These contacts in turns close and complete the circuit breaker trip coil circuit hence make the circuit breaker tripped for disconnecting the faulty portion of the electrical circuit from rest of the healthy circuit. 
Now let’s have a discussion on some terms related to protective relay.
Pickup level of actuating signal: The value of actuating quantity (voltage or current) which is on threshold above which the relay initiates to be operated.
If the value of actuating quantity is increased, the electromagnetic effect of the relay coil is increased and above a certain level of actuating quantity the moving mechanism of the relay just starts to move. 
Reset level: The value of current or voltage below which a relay opens its contacts and comes in original position.
Operating time of relay -Just after exceeding pickup level of actuating quantity the moving mechanism (for example rotating disc) of relay starts moving and it ultimately close the relay contacts at the end of its journey. The time which elapses between the instant when actuating quantity exceeds the pickup value to the instant when the relay contacts close.
Reset time of relay – The time which elapses between the instant when the actuating quantity becomes less than the reset value to the instant when the relay contacts returns to its normal position.
Reach of relay – A distance relay operates whenever the distance seen by the relay is less than the pre-specified impedance. The actuating impedance in the relay is the function of distance in a distance protection relay. This impedance or corresponding distance is called reach of the relay.
Power system protection relays can be categorized into different types of relays.

Types of Relays

Types of protection relays are mainly based on their characteristic, logic, on actuating parameter and operation mechanism.
Based on operation mechanism protection relay can be categorized as electromagnetic relay, static relay and mechanical relay. Actually relay is nothing but a combination of one or more open or closed contacts. These all or some specific contacts the relay change their state when actuating parameters are applied to the relay. That means open contacts become closed and closed contacts become open. In electromagnetic relay these closing and opening of relay contacts are done by electromagnetic action of a solenoid. 
In mechanical relay these closing and opening of relay contacts are done by mechanical displacement of different gear level system.
In static relay it is mainly done by semiconductor switches like thyristor. In digital relay on and off state can be referred as 1 and 0 state. 
Based on Characteristic the protection relay can be categorized as-
  1. Definite time relays
  2. Inverse time relays with definite minimum time(IDMT)
  3. Instantaneous relays.
  4. IDMT with inst.
  5. Stepped characteristic.
  6. Programmed switches.
  7. Voltage restraint over current relay.

Based on of logic the protection relay can be categorized as-
  1. Differential.
  2. Unbalance.
  3. Neutral displacement.
  4. Directional.
  5. Restricted earth fault.
  6. Over fluxing.
  7. Distance schemes.
  8. Bus bar protection.
  9. Reverse power relays.
  10. Loss of excitation.
  11. Negative phase sequence relays etc.

Based on actuating parameter the protection relay can be categorized as-
  1. Current relays.
  2. Voltage relays.
  3. Frequency relays.
  4. Power relays etc.

Based on application the protection relay can be categorized as-
  1. Primary relay.
  2. Backup relay.

Primary relay or primary protection relay is the first line of power system protection whereas backup relay is operated only when primary relay fails to be operated during fault. Hence backup relay is slower in action than primary relay. Any relay may fail to be operated due to any of the following reasons,
  1. The protective relay itself is defective.
  2. DC Trip voltage supply to the relay is unavailable.
  3. Trip lead from relay panel to circuit breaker is disconnected.
  4. Trip coil in the circuit breaker is disconnected or defective.
  5. Current or voltage signals from CT or PT respectively is unavailable.
As because backup relay operates only when primary relay fails, backup protection relay should not have anything common with primary protection relay.
Some examples of Mechanical Relay are-
  1. Thermal
  2. (a) OT trip (Oil Temperature Trip)
    (b) WT trip (Winding Temperature Trip)
    (C) Bearing temp trip etc.

  3. Float type
  4. (a) Buchholz
    (b) OSR
    (c) PRV
    (d) Water level Controls etc.

  5. Pressure switches.
  6. Mechanical interlocks.
  7. Pole discrepancy relay.

Relay Setting Calculation



"" Just An Example For a post ""

During study of electrical protective relays, some special terms are frequently used. For proper understanding, the functions of different protective relays, the definition of such terms must be understood properly. Such terms are,


  1. Pick up current.
  2. Current setting.
  3. Plug setting multiplier (PSM).
  4. Time setting multiplier (TSM).

Pick Up Current of Relay

In all electrical relays, the moving contacts are not free to move. All the contacts remain in their respective normal position by some force applied on them continuously. This force is called controlling force of the relay. This controlling force may be gravitational force, may be spring force, may be magnetic force. The force applied on the relay’s moving parts for changing the normal position of the contacts, is called deflecting force. This deflecting force is always in opposition of controlling force and presents always in the relay. Although the deflecting force always presents in the relay directly connected to live line, but as the magnitude of this force is less than controlling force in normal condition, the relay does not operate. If the actuating current in the relay coil increases gradually, the deflecting force in electro mechanical relay, is also increased. Once, the deflecting force crosses the controlling force, the moving parts of the relay initiate to move to change the position of the contacts in the relay. The current for which the relay initiates it operation is called pick up current of relay.

Current Setting of Relay

The minimum pick up value of the deflecting force of an electrical relay is constant. Again the deflecting force of the coil is proportional to its number of turns and current flowing through the coil.
Now, if we can change the number of active turns of any coil, the required current to reach at minimum pick value of the deflecting force, in the coil also changes. That means if active turns of the relay coil is reduced, then proportionately more current is required to produce desired relay actuating force. Similarly if active turns of the relay coil is increased, then proportionately reduced current is required to produce same desired deflecting force.
Practically same model relays may be used in different systems. As per these systems requirement the pick up current of relay is adjusted. This is known as current setting of relay. This is achieved by providing required number of tapping in the coil. These taps are brought out to a plug bridge. The number of active turns in the coil can be changed by inserting plug in different points in the bridge.
The current setting of relay is expressed in percentage ratio of relay pick up current to rated secondary current of CT.
That means,


For example, suppose, you want that, an over current relay should operate when the system current just crosses 125% of rated current. If the relay is rated with 1 A, the normal pick up current of the relay is 1 A and it should be equal to secondary rated current of current transformer connected to the relay.

Then, the relay will be operated when the current of CT secondary becomes more than or equal 1.25 A.
As per definition,


The current setting is sometimes referred as current plug setting.

The current setting of over current relay is generally ranged from 50% to 200%, in steps of 25%. For earth fault relay it is from 10% to 70% in steps of 10%.

Plug Setting Multiplier of Relay

Plug setting multiplier of relay is referred as ratio of fault current in the relay to its pick up current.


Suppose we have connected on protection CT of ratio 200/1 A and current setting is 150%.

Hence, pick up current of the relay is, 1 × 150 % = 1.5 A
Now, suppose fault current in the CT primary is 1000 A. Hence, fault current in the CT secondary i.e. in the relay coil is, 1000 × 1/200 = 5 A
Therefore PSM of the relay is, 5 / 1.5 =3.33

Time Setting Multiplier of Relay

The operating time of an electrical relay mainly depends upon two factors :
  1. How long distance to be traveled by the moving parts of the relay for closing relay contacts and
  2. How fast the moving parts of the relay cover this distance.
So far adjusting relay operating time, both of the factors to be adjusted.
The adjustment of travelling distance of an electromechanical relay is commonly known as time setting. This adjustment is commonly known as time setting multiplier of relay. The time setting dial is calibrated from 0 to 1 in steps 0.05 sec.
But by adjusting only time setting multiplier, we can not set the actual time of operation of an electrical relay. As we already said, the time of operation also depends upon the speed of operation. The speed of moving parts of relay depends upon the force due to current in the relay coil. Hence it is clear that, speed of operation of an electrical relay depends upon the level of fault current. In other words, time of operation of relay depends upon plug setting multiplier. The relation between time of operation and plug setting multiplier is plotted on a graph paper and this is known as time / PSM graph. From this graph one can determine, the total time taken by the moving parts of an electromechanical relay, to complete its total travelling distance for different PSM. In time setting multiplier, this total travelling distance is divided and calibrated from 0 to 1 in steps of 0.05.
So when time setting is 0.1, the moving parts of the relay has to travel only 0.1 times of the total travelling distance, to close the contact of the relay. So, if we get total operating time of the relay for a particular PSM from time / PSM graph and if we multiply that time with the time setting multiplier, we will get, actual time of operation of relay for said PSM and TSM.
For getting clear idea, let us have a practical example. Say a relay has time setting 0.1 and you have to calculate actual time of operation for PSM 10.
From time / PSM graph of the relay as shown below, we can see the total operating time of the relay is 3 seconds. That means, the moving parts of the relay take total 3 seconds to travel 100% travelling distance. As the time setting multiplier is 0.1 here, actually the moving parts of the relay have to travel only 0.1 × 100% or 10% of the total travel distance, to close the relay contacts.
Hence, actual operating time of the relay is 3 × 0.1 = 0.3 sec. i.e. 10% of 3 sec.

Time vs PSM Curve of Relay

This is relation curve between operating time and plug setting multiplier of an electrical relay. The x-axis or horizontal axis of the Time / PSM graph represents, PSM and Y-axis or vertical axis represents time of operation of the relay. The time of operation represents in this graph is that, which required to operate the relay when time setting multiplier set at 1.
From the Time / PSM curve of a typical relay shown below, it is seen that, if PSM is 10, the time of operation of relay is 3 sec. That means, the relay will take 3 seconds to complete its operation, with time setting 1.
It is also seen from the curve that, for lower value of plug setting multiplier, i.e. for lower value of fault current, the time of operation of the relay is inversely proportional to the fault current.
But when PSM becomes more than 20, the operating time of relay becomes almost constant. This feature is necessary in order to ensure discrimination on very heavy fault current flowing through sound feeders.

Calculation of Relay Operation Time

For calculating actual relay operating time, we need to know these following operation.
  1. Current setting.
  2. Fault current level.
  3. Ratio of current transformer.
  4. Time / PSM curve.
  5. Time setting.
Step – 1
From CT ratio, we first see the rated secondary current of CT. Say the CT ratio is 100 / 1 A, i.e. secondary current of CT is 1 A.
Step – 2 
From current setting we calculate the trick current of the relay. Say current setting of the relay is 150% therefore pick up current of the relay is 1 × 150% = 1.5 A.
Step – 3
Now we have to calculate PSM for the specified faulty current level. For that, we have to first divide primary faulty current by CT ratio to get relay faulty current. Say the faulty current level is 1500 A, in the CT primary, hence secondary equivalent of faulty current is 1500/(100/1) = 15 A

Step – 4
Now, after calculating PSM, we have to find out the total time of operation of the relay from Time / PSM curve. From the curve, say we found the time of operation of relay is 3 second for PSM = 10.
Step – 5
Finally that operating time of relay would be multiplied with time setting multiplier, in order to get actual time of operation of relay. Hence say time setting of the relay is 0.1.
Therefore actual time of operation of the relay for PSM 10, is 3 × 0.1 = 0.3 sec or 300 ms. 

Electrical Fault Calculation


"" JUST AN EXAMPLE ""

 Before applying proper electrical protection system, it is necessary to have through knowledge of the conditions of electrical power system during faults. The knowledge of electrical fault condition is required to deploy proper different protective relays in different locations of electrical power system.

Information regarding values of maximum and minimum fault currents, voltages under those faults in magnitude and phase relation with respect to the currents at different parts of power system, to be gathered for proper application of protection relay system in those different parts of the electrical power system. Collecting the information from different parameters of the system is generally known as electrical fault calculation .

------------------------------------------------------------------------

Fault calculation broadly means calculation of fault current in any electrical power system. There are mainly three steps for calculating faults in a system.
  1. Choice of impedance rotations.
  2. Reduction of complicated electrical power system network to single equivalent impedance.
  3. Electrical fault currents and voltages calculation by using symmetrical component theory.

Impedance Notation of Electrical Power System

If we look at any electrical power system, we will find, these are several voltage levels. For example, suppose a typical power system where electrical power is generated at 6.6 kV then that 132 kV power is transmitted to terminal substation where it is stepped down to 33 kV and 11 kV levels and this 11 kV level may further step down to 0.4kv. Hence from this example it is clear that a same power system network may have different voltage levels. So calculation of fault at any location of the said system becomes much difficult and complicated it try to calculate impedance of different parts of the system according to their voltage level. This difficulty can be avoided if we calculate impedance of different part of the system in reference to a single base value. This technique is called impedance notation of power system. In other wards, before electrical fault calculation, the system parameters, must be referred to base quantities and represented as uniform system of impedance in either ohmic, percentage, or per unit values.
Electrical power and voltage are generally taken as base quantities. In three phase system,three phase power in MVA or KVA is taken as base power and line to line voltage in KV is taken as base voltage. The base impedance of the system can be calculated from these base power and base voltage, as follows,


Per unit is an impedance value of any system is nothing but the radio of actual impedance of the system to the base impedance value.


Percentage impedance value can be calculated by multiplying 100 with per unit value.



Again it is sometimes required to convert per unit values referred to new base values for simplifying different electrical fault calculations. In that case,


The choice of impedance notation depends upon the complicity of the system. Generally base voltage of a system is so chosen that it requires minimum number of transfers.
Suppose, one system as a large number of 132 KV over head lines, few numbers of 33 KV lines and very few number of 11 KV lines. The base voltage of the system can be chosen either as 132 KV or 33 KV or 11 KV, but here the best base voltages 132 KV, because it requires minimum number of transfer during fault calculation.

Network Reduction

After choosing the correct impedance notation, the next step is to reduce network to a single impedance. For this first we have to convert the impedance of all generators, lines, cables, transformer to a common base value. Then we prepare a schematic diagram of electrical power system showing the impedance referred to same base value of all those generators, lines, cables and transformers.
The network then reduced to a common equivalent single impedance by using star/delta transformations. Separate impedance diagrams should be prepared for positive, negative and zero sequence networks.
There phase faults are unique since they are balanced i.e. symmetrical in three phase, and can be calculated from the single phase positive sequence impedance diagram. Therefore three phase fault current is obtained by,


Where I f is the total three phase fault current, v is the phase to neutral voltage z 1 is the total positive sequence impedance of the system; assuming that in the calculation, impedance are represented in ohms on a voltage base.

Symmetrical Component Analysis

The above fault calculation is made on assumption of three phase balanced system. The calculation is made for one phase only as the current and voltage conditions are same in all three phases. When actual faults occur in electrical power system, such as phase to earth fault, phase to phase fault and double phase to earth fault, the system becomes unbalanced means, the conditions of voltages and currents in all phases are no longer symmetrical. Such faults are solved by symmetrical component analysis. Generally three phase vector diagram may be replaced by three sets of balanced vectors. One has opposite or negative phase rotation, second has positive phase rotation and last one is co-phasal. That means these vectors sets are described as negative, positive and zero sequence, respectively.
positive negative zero sequence voltage


The equation between phase and sequence quantities are,


Therefore,


Where all quantities are referred to the reference phase r
Similarly a set of equations can be written for sequence currents also. From , voltage and current equations, one can easily determine the sequence impedance of the system. The development of symmetrical component analysis depends upon the fact that in balanced system of impedance, sequence currents can give rise only to voltage drops of the same sequence. Once the sequence networks are available, these can be converted to single equivalent impedance.
Let us consider Z1, Z2 and Z0 are the impedance of the system to the flow of positive, negative and zero sequence current respectively. 
For earth fault


Phase to phase faults



Double phase to earth faults


Three phase faults


If fault current in any particular branch of the network is required, the same can be calculated after combining the sequence components flowing in that branch. This involves the distribution of sequence components currents as determined by solving the above equations, in their respective network according to their relative impedance. Voltages it any point of the network can also be determine once the sequence component currents and sequence impedance of each branch are known. 

Sequence Impedance

Positive Sequence Impedance

The impedance offered by the system to the flow of positive sequence current is calledpositive sequence impedance 

Negative Sequence Impedance

The impedance offered by the system to the flow of negative sequence current is callednegative sequence impedance .

Zero Sequence Impedance

The impedance offered by the system to the flow of zero sequence current is known aszero sequence impedance .
In previous fault calculation, Z1, Z2 and Z0 are positive, negative and zero sequence impedance respectively. The sequence impedance varies with the type of power system components under consideration:- 
  1. In static and balanced power system components like transformer and lines, thesequence impedance offered by the system are the same for positive and negative sequence currents. In other words, the positive sequence impedance and negative sequence impedance are same for transformers and power lines.
  2. But in case of rotating machines the positive and negative sequence impedanceare different.
  3. The assignment of zero sequence impedance values is a more complex one. This is because the three zero sequence current at any point in a electrical power system, being in phase, do not sum to zero but must return through the neutral and /or earth. In three phase transformer and machine fluxes due to zero sequence components do not sum to zero in the yoke or field system. The impedance very widely depending upon the physical arrangement of the magnetic circuits and winding.
    1. The reactance of transmission lines of zero sequence currents can be about 3 to 5 times the positive sequence current, the lighter value being for lines without earth wires. This is because the spacing between the go andreturn(i.e. neutral and/or earth) is so much greater than for positive and negative sequence currents which return (balance) within the three phase conductor groups.
    2. The zero sequence reactance of a machine is compounded of leakage and winding reactance, and a small component due to winding balance (depends on winding tritch).
    3. The zero sequence reactance of transformers depends both on winding connections and upon construction of core.